Products » Systems
LOOSE-LAID/BALLASTED SYSTEM - HEAVY TRAFFIC
1. SUBSTRATE
Typical: structural concrete
-
The structure will be designed to support the paving slab and the traffic.
-
The substrate will be clean, dry, smooth and free from contamination.
-
Although dead level is acceptable, a slope is recommended for roof drainage.
-
All vertical surfaces will be compatible with Rubberfuse
Flashing/Substrate Adhesive*.
* Refer to technical data sheet.
2. VAPOUR CONTROL LAYER
Typical: 200µ polyethylene film
-
The material type will be specified as required by the dew point calculation.
-
Install PE loose-laid with 100 mm overlap and taped seam, other types as specified by manufacturer.
3. INSULATION
Typical: 25 kg/m² expanded polystyrene
-
Any UEAtc approved roofing board with the required thickness is also acceptable.
-
Install loose with staggered joints, avoiding gaps in excess of 6mm.
-
Taper the joints at roofdrains.
-
Should insulation not be used (concrete),a protection layer (geotextile 300-400 g/m²) should be installed.
4. SINTOFOIL MEMBRANE
Typical: ST/Black/1.2 mm
-
Any other type of Sintofoil membrane is also acceptable.
-
Install loose, with overlap and welded seam as per specifications*.
* Refer to the "welded seam technology" section
5. SEPARATION LAYER
Typical: 200µ min. polyethylene film.
-
Install loose, with min. 100 mm overlap.
6.PROTECTION LAYER
Typical: 30mm protection course.
-
Install loose, with butted joints covered by a self-adhesive tape.
7. PAVING SLAB
Typical: tiles on cement/sand bed.
-
Install loose, with butted joints covered by a self-adhesive tape.
Notes:
Refer to the local code requirements when applicable.
Reroofing projects will be subject to a specific study, including preliminary inspection.