Products » Systems
MECHANICALLY ATTACHED ROOFING SYSTEM (FIXING BAR OPTION)
1. SUBSTRATE
Typical: structural concrete
-
The substrate will provide for the required fasteners' minimum pull-out resistance: steeldeck: 1.700 N plywood: 2.000 N concrete: 2.500 N
-
Concrete: the substrate will be clean, dry, smooth and free from contaminants.
-
Although dead level is acceptable, a slope is recommended for roof drainage.
-
All vertical surfaces will be compatible with the Flashing/Substrate Adhesive.*
* Refer to technical data sheet
2.VAPOUR CONTROL LAYER
Typical: 200µ polyethylene film
-
The material type will be specified if/as required by the dew point calculation.
-
Install PE loose-laid with 100mm overlap and taped seam, other types as specified by manufacturer.
3. INSULATION
Typical: Class C mineral wool
-
Any Class C or Class D UEAtc approved roofing board with the required thickness is also acceptable.
-
The boards will be mechanically secured as per the insulation manufacturer's recommendations.
-
Taper the joints at roofdrains.
-
Should insulation not be used (concrete), a protection layer (geotextile 300-400 g/m²) should be installed.
4.SINTOFOIL MEMBRANE
Typical: ST/Grey/1.2 mm
-
Install the membrane with overlap and welded seam as per specifications.*
-
Mechanically secure the membrane to the deck according to the wind uplift pattern using fixing bars and approved fasteners.
-
Cover the fixing bars with a Sintofoil ST/1.2 mm strip (min. 150 mm) welded on both sides to membrane.
-
The membrane will be mechanically secured at roof perimeter and around protrusions.
-
The RG type membrane is recommended, would aesthetics (wrinkles) be an issue.
* Refer to "welded seam technology" section
5.TRAFFIC
Typical: smooth round river washed gravel, ø 12-35 mm, 60kg/m² min.
-
The installed membrane will be protected from following other trades' work.
-
Walkways (if required): SLM walkways or a 1.5 mm Sintofoil roll 1.05 m wide, welded to the membrane.
Notes:
The architect is responsible for the wind study and the resulting fastening pattern.
Refer to the local code requirements when applicable. Reroofing projects will be subject to a specific study, including preliminary inspection and pull-out testings.